AGLD Series Ground Fault Relays with Digital Display
AGLD relays display the adjustable trip point and delay while monitoring AC ground leakage. Choose a 5–100 mA or 80–950 mA range with SPDT relay output, a 24 V AC/DC supply and a 1.76 in (44.7 mm) maximum wire bundle.
| Base Model # | Case Style | Setpoint Range | Sensing Aperature Size | Response Time | Output Types / Ratings | Normally In Stock | Add to Cart / Configure Part # |
| AGLD | Solid Core | 5–100 or 80–950 mA | 1.76 in (44.7 mm) | 120 ms | SPDT relay; auto-reset or latching | Inquire | Configurator |
24 V AC/DC (20–30 V)
AGLD1: 5–100 mA; AGLD2: 80–950 mA, field adjustable
1 A at 120 V AC; 2 A at 30 V DC maximum
Up to 1 second, adjustable after startup
50–60 Hz
−20 to 40°C surrounding air; 0–95% RH, non-condensing
1.76 in (44.7 mm)
<4 VA
Electromechanical SPDT relay
120 ms
1240 V AC (catalogue rating)
Solid-core; UL94 V-0 flammability-rated housing
UL/cUL, CE
The current models use 24 V AC/DC power only. Choose DEN or ENE auto-reset operation, or LA latching with manual reset. The adjustable delay is up to one second, in addition to the response time. Example: AGLD1-SDT1-24U-ENE-ADJ.
Pass all current-carrying conductors of the monitored circuit through the sensing window. Follow the installation sheet for conductor arrangement, grounding and external trip-device wiring. The sensor provides a detection/contact signal; use it as part of a suitable protection system.