AGF-FM Series Ground Fault Relays


AGF-FM ground-fault relays offer fixed 5 mA or 20 mA trip points, a 1.25 in (31.75 mm) maximum wire bundle and an SPDT dry-contact auto-reset output. They use a 120 V AC supply and include remote TEST terminals for installations using compatible trip equipment.


Select & Configure Model
Base Model #Case StyleSetpoint RangeSensing Aperature SizeResponse TimeOutput Types / RatingsNormally
In Stock
Configure Part #
 
AGF-SDTR-120-ENE-005-FMSolid Core5 mA fixed1.25 in (31.75 mm)See response curveSPDT dry contact; remote TESTInquire
AGF-SDTR-120-ENE-020-FMSolid Core20 mA fixed1.25 in (31.75 mm)See response curveSPDT dry contact; remote TESTInquire
Power Supply:

120 V AC ±10%

Setpoint range:

5 mA ±5%, or 20 mA +0%/−10%, fixed factory set

Output Ratings:

2 A at 120 V AC; 2 A at 30 V DC general use

Time Delay:

None specified

Frequency Range:

50–60 Hz; monitored circuit up to 600 V AC

Environmental:

−20 to 50°C; 0–95% RH, non-condensing

Maximum Wire Bundle Diameter:

1.25 in (31.75 mm)

Power Consumption:

2.3 VA maximum

Output(s):

SPDT dry-contact Form C relay, normally energized, auto-reset; remote TEST

Response Time:

See catalogue response curves for 5 mA and 20 mA versions

Isolation Voltage:

2200 V AC

Case:

Solid-core; UL94 V-0 flammability-rated housing

Approvals:

UL/cUL Listed to UL 508 (NRNT.E129625), CE


Choose AGF-SDTR-120-ENE-005-FM for 5 mA or AGF-SDTR-120-ENE-020-FM for 20 mA. The normally energized relay changes state on a fault or loss of control power when installed as specified. Suitable applications include equipment under exhaust hoods; follow the instruction sheet for the external shunt-trip circuit.

Pass all current-carrying conductors of the monitored circuit through the sensing window. Follow the installation sheet for conductor arrangement, grounding and external trip-device wiring. The sensor provides a detection/contact signal; use it as part of a suitable protection system.


Mod Tronic Instruments Limited
1 Delta Park Blvd #12
Brampton, ON L6T 5G1
Phone: 905-457-6322 or 1-800-794-5883
Fax: 905-457-4716 or 1-800-830-7122
Brampton
Halifax
Regina
Edmonton
905-457-6322
902-422-0978
306-359-1476
780-459-2690
Montreal
Winnipeg
Calgary
Vancouver
514-848-7205
204-895-2038
403-236-2909
604-224-9547