AGK-FM Series Ground Fault Relay
AGK-FM detects a fixed 5 mA AC ground fault and provides a normally open 120 V AC wet-contact output for a compatible shunt-trip circuit. The 1.25 in (31.75 mm) maximum bundle diameter accommodates multiple current-carrying conductors.
| Base Model # | Case Style | Setpoint Range | Sensing Aperature Size | Response Time | Output Types / Ratings | Normally In Stock | Configure Part # |
| AGK-SSTPR-120-DEN-005-FM | Solid Core | 5 mA fixed | 1.25 in (31.75 mm) | 150 ms at 5% over setpoint | SPST 120 V AC wet contact; remote TEST | Inquire |
120 V AC ±10%; line polarity sensitive
5.0 mA, ±5%, fixed
2 A at 120 V AC general use, wet contact
None specified
50–60 Hz; monitored circuit up to 600 V AC
−20 to 50°C; 0–95% RH, non-condensing
1.25 in (31.75 mm)
2.3 VA maximum
SPST normally open wet-contact relay, auto-reset; remote TEST terminals
150 ms at 5% above setpoint; see response curve
2200 V AC
Solid-core; UL94 V-0 flammability-rated housing
UL/cUL Listed to UL 508 (NRNT.E129625), CE
Fixed standard model: AGK-SSTPR-120-DEN-005-FM. The line supply is internally connected to the relay output; this is a wet-contact output, not an isolated dry contact. It includes local and remote TEST connections. Line and neutral supply polarity must be observed.
Pass all current-carrying conductors of the monitored circuit through the sensing window. Follow the installation sheet for conductor arrangement, grounding and external trip-device wiring. The sensor provides a detection/contact signal; use it as part of a suitable protection system.