AGT-FL Series Ground Fault Transducers


AGT-FL transducers measure AC residual current and provide a true-RMS 4–20 mA output. Choose a 0–50 mA or 0–100 mA factory-calibrated range in a solid-core housing for wire bundles up to 0.75 in (19.1 mm).


Select & Configure Model
Base Model #Case StyleSetpoint RangeSensing Aperature SizeResponse TimeOutput Types / RatingsNormally
In Stock
Add to Cart /
Configure Part #
 
AGT1-420-24L-FLSolid Core0–50 mA0.75 in (19.1 mm)600 ms4–20 mA true RMSInquire
AGT2-420-24L-FLSolid Core0–100 mA0.75 in (19.1 mm)600 ms4–20 mA true RMSInquire
Power Supply:

24 V DC loop-powered (12–32 V)

Output(s):

4–20 mA, true-RMS response; output limit 23 mA

Response Time:

600 ms to 90% of step change

Isolation Voltage:

Tested to 2200 V AC

Case:

Solid-core, top terminals; UL94 V-0 housing

Approvals:

UL/cUL

Power Consumption:

<2 VA

Output Loads:

600 Ω maximum at 24 V DC

Input:

0–50 mA or 0–100 mA AC residual current

Frequency Range:

40–400 Hz

Environmental:

−20 to 40°C; 0–95% RH, non-condensing

Maximum Wire Bundle Diameter:

0.75 in (19.1 mm)


The two standard models are AGT1-420-24L-FL (0–50 mA) and AGT2-420-24L-FL (0–100 mA). Supply is nominally 24 V DC, loop-powered, with a 12–32 V operating range. Custom ranges are available by inquiry.

For residual-current measurement, pass all current-carrying conductors through the sensing window. The output is a measurement signal for an external controller or data logger; the transducer does not provide an integral trip relay.


Mod Tronic Instruments Limited
1 Delta Park Blvd #12
Brampton, ON L6T 5G1
Phone: 905-457-6322 or 1-800-794-5883
Fax: 905-457-4716 or 1-800-830-7122
Brampton
Halifax
Regina
Edmonton
905-457-6322
902-422-0978
306-359-1476
780-459-2690
Montreal
Winnipeg
Calgary
Vancouver
514-848-7205
204-895-2038
403-236-2909
604-224-9547