AGV Series Ground Fault Relays for VFD Loads
AGV relays detect AC ground leakage on variable-frequency driven loads over a 12–398 Hz monitored-circuit frequency range. Select 30, 50 or 100 mA at the device and an adjustable 0–10 second delay. The maximum wire-bundle diameter is 0.75 in (19.1 mm).
| Base Model # | Case Style | Setpoint Range | Sensing Aperature Size | Response Time | Output Types / Ratings | Normally In Stock | Add to Cart / Configure Part # |
| AGV3-SDT | Solid Core | 30/50/100 mA selectable | 0.75 in (19.1 mm) | Frequency-dependent; see Specs | SPDT relay, auto-reset or latching | Inquire | Configurator |
120 V AC (90–130 V) or 24 V AC/DC (19–24 V)
30, 50 or 100 mA, field switch selectable
1 A at 125 V AC; 2 A at 30 V DC resistive
0–10 seconds plus response time
12–398 Hz
−20 to 50°C; 0–95% RH, non-condensing
0.75 in (19.1 mm)
24 V version: 2.4 VA maximum; 120 V version: 3.0 VA maximum
SPDT Form C relay; auto-reset or latching
<140 ms below 17 Hz; <75 ms at 17–32 Hz; <45 ms above 32 Hz
1250 V AC; tested to 5 kV
Solid-core; UL94 V-0 flammability-rated housing
UL/cUL
The AGV3-SDT model uses an SPDT relay, a 120 V AC or 24 V AC/DC supply, and DEN or ENE auto-reset operation or LA latching operation. The TR3 suffix identifies the 30/50/100 mA selection. Example: AGV3-SDT-120-LA-TR3. Only current-carrying conductors pass through the window; follow the installation instructions for VFD applications.
Pass all current-carrying conductors of the monitored circuit through the sensing window. Follow the installation sheet for conductor arrangement, grounding and external trip-device wiring. The sensor provides a detection/contact signal; use it as part of a suitable protection system.