DG Series DC Ground Fault Relays
DG relays detect 5–40 mA of DC ground-fault current in earth-grounded systems. The solid-core sensor accommodates a 0.75 in (19.1 mm) wire bundle and offers SPDT auto-reset or N.O./N.C. SPST latching outputs from a 24 V DC supply.
| Base Model # | Case Style | Setpoint Range | Sensing Aperature Size | Response Time | Output Types / Ratings | Normally In Stock | Add to Cart / Configure Part # |
| DG1 | Solid Core | 5–40 mA DC, factory set | 0.75 in (19.1 mm) | 55 ms maximum | SPDT auto-reset or SPST latching relay | Inquire | Configurator |
24 V DC (20–26 V)
5–40 mA DC, factory set
1 A at 120 V AC; 2 A at 30 V DC maximum
None specified
DC
−20 to 50°C; 0–95% RH, non-condensing
0.75 in (19.1 mm)
<4 VA
SPDT auto-reset relay or N.O./N.C. SPST latching relay
55 ms maximum
Tested to 3 kV
Solid-core; UL94 V-0 flammability-rated housing
No agency listing specified in current catalogue
Select a factory trip point from 005 to 040 mA. SDT is auto-reset and uses DEN or ENE; NOR/NCR are latching and require LA. Example: DG1-SDT-24D-ENE-010. Intended for use on earth-grounded systems only. The current catalogue does not specify an agency listing.
Pass all current-carrying conductors of the monitored circuit through the sensing window. Follow the installation sheet for conductor arrangement, grounding and external trip-device wiring. The sensor provides a detection/contact signal; use it as part of a suitable protection system.